- SCADA Definition: SCADA is defined as Supervisory Control and Data Acquisition, a system used for high-level process control and data management.
- Components: A SCADA system includes Master Terminal Units (MTUs), Remote Terminal Units (RTUs), and communication networks for data transfer.
- Functions: SCADA systems monitor real-time data, control processes, and store information for analysis and decision-making.
- SCADA in Power Systems: SCADA in power systems helps manage current flow, voltage levels, and circuit breakers to maintain the power grid.
- Applications: SCADA systems are used across various industries for automation and control, including oil and gas, manufacturing, and water treatment.
What is SCADA?
SCADA stands for “Supervisory Control and Data Acquisition.” It is a control system that uses computers, networked data communications, and graphical Human Machine Interfaces (HMIs) to manage and control industrial processes.
SCADA systems communicate with other devices, such as programmable logic controllers (PLCs) and PID controllers to interact with industrial process plants and equipment.
SCADA systems are crucial in control systems engineering. They collect and analyze real-time data from processes, record and log this data, and display it on various graphical interfaces (HMIs).
This enables process control operators to supervise (the “S” in SCADA) what is happening in the field, even from a distant location. It also enables operators to control (the “C” in SCADA) these processes by interacting with the HMI.

Supervisory Control and Data Acquisition systems (SCADA) are essential to a wide range of industries and are broadly used for controlling and monitoring processes. They are prominently used because they have the power to control, monitor, and transmit data in a smart and seamless way.
In today’s data-driven world, we are always looking for ways to increase automation and make smarter decisions through the proper use of data, and SCADA systems are a great way of achieving this.
SCADA systems can be operated remotely, allowing operators to monitor and control processes from anywhere.
SCADA can be used efficiently to save time. One excellent example is SCADA systems, which are extensively used in the oil and gas sector. Large pipelines transport oil and chemicals inside the manufacturing unit.
Hence, safety plays a crucial role, so there should be no leakage along the pipeline. If some leakage occurs, a SCADA system is used to identify the leakage. It infers the information, transmits it to the system, displays the information on the computer screen, and gives the operator an alert.

Generic SCADA systems contain both hardware and software components. The computer used for analysis should be loaded with SCADA software. The hardware collects input data and sends it to the system for analysis.
The SCADA system contains a hard disk, which records and stores the data into a file, which is then printed when needed by the human operator. Structured Text programming is often used in SCADA systems to write control logic for PLCs, enabling more sophisticated and flexible process automation.
SCADA systems are used in various industries and manufacturing units, such as energy, food and beverage, oil and gas, power, water, and waste management units.
SCADA History
Prior to the birth of SCADA systems, manufacturing floors and industrial plants relied on manual control and monitoring using push buttons and analogue equipment. As the size of the industries and manufacturing units grew, they started using relays and timers that provided supervisory control to a certain extent.
Unfortunately, relays and timers could solve problems only with minimal automation functionality, and reconfiguring the system was difficult. So, a more efficient and fully automated system was required by all industries.
Computers were developed for industrial control purposes in the early 1950s. Slowly, the concept of telemetry was introduced for virtual communication and data transmission.
Around 1970, the term SCADA was coined along with the evolution of microprocessors and PLC concepts.
This helped develop a fully automated system that can be used remotely in the industry. As the years rolled by, distributed SCADA systems were developed in the early 2000s.
Modern SCADA systems have come into existence and allowed us to control and monitor real-time data anywhere in the world.
The real-time interaction boomed up the business and took the growth of industries to greater heights. Even if the operator did not have much knowledge of software development, he was able to manage modern SCADA systems.
SCADA Basics
Objectives of SCADA
- Monitor: SCADA systems continuously monitor the physical parameters
- Measure: It measures the parameter for processing
- Data Acquisition: It acquires data from RTUs (Remote Terminal Units), data loggers, etc
- Data Communication: It helps to communicate and transmit a large amount of data between MTU and RTU units
- Controlling: Online real-time monitoring and control of the process
- Automation: It helps for automatic transmission and functionality
The SCADA systems consist of hardware units and software units. SCADA applications are run on a server. Desktop computers and screens act as HMIs that are connected to the server. The major components of a SCADA system include the following:
- Master Terminal Unit (MTU)
- Remote Terminal Unit (RTU)
- Communication Network (defined by its network topology).

Master Terminal Unit (MTU)
MTU is the core of the SCADA system. It comprises a computer, a PLC, and a network server that helps the MTU communicate with the RTUs. MTU begins communication, collects and saves data, helps to interface with operators, and communicates data to other systems.
Remote Terminal Unit (RTU)
Being employed in the field sites, each Remote Terminal Unit (RTU) is connected with sensors and actuators. RTU is used to collect information from these sensors and further send the data to MTU. RTUs have a storage capacity facility.
It stores the data and transmits it when the MTU commands. Modern RTUs use PLCs for direct data transfer and control, often without signals from the MTU.

Communication Network
In general, network means connection. When you describe a communication network, it is defined as a link between an RTU in the field and an MTU in the central location. The bidirectional wired or wireless communication channel is used for networking purposes. Various other communication mediums, like fibre optic cables, twisted pair cables, etc., are also used.
Functions of SCADA Systems
In a nutshell, the SCADA system is a collection of hardware and software components that allows the manufacturing units to perform specific functions. Some of the important functions include
- To monitor and gather data in real-time
- To interact with field devices and control stations via Human Machine Interface (HMI),
- To record systems events into a log file
- To control the manufacturing processes virtually
- Information Storage and Reports
SCADA Software
As discussed earlier, SCADA software plays a significant role in the whole process analysis. Several big manufacturing companies work exclusively on SCADA software. Many factors must be looked at before the SCADA software is selected and implemented. To mention a few,
- The lifespan of the software: Since you are going to invest a lot in procuring the software, it is always better to check if the software will last between 5 to 10 years down the lane.
- Request for Information: It is a business term used to specify details about vendors and suppliers. If you buy software from a particular vendor, he or she should be able to give you technical support whenever required.
- Historian Software: The term historian means the software should save data with timestamps that can be used for future reference. So, your software should be proficient in handling and logging data from the field.
- SCADA technology: As we all know, technology is growing rapidly so as to meet our needs. When you mean technology, it does not imply that you always need to use the latest technology that pops up in the market. Rather, you should choose a technology that can stay stable and secure for a longer time.
- Alarm Supervision and Management: Almost all SCADA systems have an alarming feature that comes along with software development. The configuration of the alarm is important. There are two types of alarm systems: system-defined alarms, which are managed by the system itself, and user-defined alarms, which are managed by the user.
Let us have a look at software developed by big players in the market.
Citect SCADA, Schneider Electric
A compact, flexible, and reliable SCADA software developed by Schneider Electric. The latest product released by them is Vijeo Citect (version 7.10) Citect SCADA is still one of the most commonly used SCADA technologies, and you certainly need to learn about this platform as a SCADA developer. It has actually become part of the SCADA alternatives for Wonderware.
InTouch – Wonderware
InTouch, which has become one of the largest SCADA suppliers on the market, comes from Wonderware, now owned by Schneider Electric. Although Wonderware is relatively new to the market, it is quickly gaining popularity.
The Wonderware system platform is a SCADA system with many “plug-and-play” parts that are modular and very versatile. Because of the modularity of this scheme, you can readily customise it to your requirements if you choose this SCADA software. The benefit of In Touch is that it uses open standards of communication and can operate with most PLC systems.
Experion SCADA – Honeywell
Honeywell is commonly used in PLC systems (particularly in the US). They are also a big player in the SCADA market, providing a software platform for programming SCADA and HMI software systems. You can either use their software for a stand-alone SCADA scheme or use it with Honeywell’s PLC platform (e.g., the C200 and C300 platforms) as well as RTUs like Control Edge RTU.
Although Honeywell’s SCADA software is optimised to communicate with other Honeywell products (e.g., PLCs and RTUs), it will still work when paired with non-Honeywell products.
iFIX – General Electric
General Electric (GE) is one of the world’s largest manufacturing businesses and is also a significant player in the SCADA market. IFIX is one of their software solutions and it is a very flexible SCADA system. The advantage of using iFIX is its ability to develop screens quickly with HTML5.
Another reason is the many drivers that allow you to set up networked and distributed systems, allowing you to connect and exchange information with most contemporary PLCs. GE also has its own branded PLCs, but a GE SCADA system does not require these GE PLCs to function correctly.
Ignition – Inductive Automation
Ignition is a SCADA scheme that uses the latest IoT architecture to its full potential. Ignition from Induction Automation is a very nice option if you want a system that is up-to-date with all Industry 4.0 norms and techniques.
Ignition is relatively new to the SCADA industry compared to some of the veteran systems. That said, between Ignition’s IoT integrations and the fact that they work with most PLC systems, Ignition has been chosen by many businesses as their SCADA solution.
SIMATIC WinCC V7 – Siemens
The Siemens SCADA system has been around for many years and is known as “WinCC.” Siemens is one of the largest players in the PLC and SCADA industries, and many businesses use the Siemens platform. Siemens is a huge company that has been evolving its PLC and SCADA platforms over the years to adopt modern technologies.
The fact that they are a large and veteran player in the SCADA industry gives many businesses confidence in entrusting them with their SCADA applications.
SCADA Applications
SCADA has made comprehensive use of features such as flexibility, reliability, and scalability in automating complex systems.
There are countless applications in the real world where SCADA has already been effective in providing surveillance and control alternatives across a broad spectrum of sectors, from energy production to agricultural systems.
SCADA is widely used in different areas, including chemical, gas, water, communications, and power systems.
Electric Power Generation, Transmission, and Distribution
Using SCADA systems, electrical utilities detect current flow and line voltage, monitor circuit breaker operation (e.g., a vacuum circuit breaker or SF6 circuit breaker), and take sections of the power grid online or offline.
Manufacturing Units
SCADA systems are used to regulate industrial automation and robots and monitor process and quality control
Mass transit and Railway Traction
Transit officials use SCADA to regulate electricity for subways, trams, and trolley buses; to automate railway traffic signals; to monitor and identify trains and buses; and to control railway crossing doors
Water, Waste Water Utilities and Sewage
State and municipal water utilities use SCADA to monitor and control water flow, tank concentrations, pipe pressure, and other variables

Buildings, Facilities, and Environments
Facility managers use SCADA to regulate HVAC, cooling, lighting, and input systems.
Water Security: The Role of the SCADA System
A lot of research continues to be performed on how to implement modern SCADA concepts into water treatment plants whilst minimizing the risk of unauthorized network access (cyber risk is an ongoing issue in large enterprises).
The communication network of SCADA is distributed across the water distribution system, as shown in the figure below. Workstations, typically PC-based, are situated at a treatment facility in a control room, enabling operators to view the entire process and take control measures.
Within the plant, programmable logic controllers are used in chemical treatment and filters. Local Area Network (LAN) is used to link the controllers to workstations. Remote terminal units (RTUs) are used in remote locations and are generally found in sensitive fields such as pump stations, storage tanks, valve vaults, and treatment centres.
The RTU communicates on a wide-area network, as typified by the radio scheme shown in the following figure. A significant benefit of SCADA schemes is the coordination of safety measures with activities. A SCADA system connected to perimeter surveillance systems can either decrease the need for manned patrols considerably or eliminate them.

The SCADA scheme can provide ongoing surveillance of all places, unlike patrols. You can easily interface security systems or appliances, including video cameras, motion detectors, contact switches, keypad entry devices, and card readers, either directly to the SCADA network or via a neighbouring remote terminal unit (RTU). Today’s SCADA systems also provide alarm management in instances where many alarms happen in a brief moment.
Thermal Power Plants
Most operational inspections of thermal power plants are automatic. However, manual action may be necessary at times. The plant is therefore equipped with monitoring and alarm systems that alert plant operators when certain working parameters deviate significantly from their normal range.
The demand for greater reliability and effectiveness is growing in thermal power plants. After periodic intervals, the power plant needs continuous inspection and tracking. There may be a chance of mistakes when human employees measure at different phases.
To improve reliability, automation is required to improve the general power plant efficiency. Automation is established through the use of PLC and SCADA, which decreases human workers’ mistakes. SCADA system is used to supervise a complete process

Forestry, Pulp and Paper Industry
The forestry, pulp, and paper industries also rely on SCADA systems. From automation and process control to energy management, drive control, power protection, enclosure systems, and safety, the industry has ample uses for SCADA.
SCADA systems are used throughout the paper supply chain, including within the wood yard, chippers, evaporators, digestors, refiners, cleaners, drying and pressing, and, of course, paper machines. This complex processing of trees into paper is automated from end to end through the use of established SCADA systems.
Difference Between PLC and SCADA
SCADA and PLCs can easily be confused when you’re first learning about control engineering. You will often hear the terms “PLC” and “SCADA” used within the same breath. Although they are related, they are distinctly different from one another.
A PLC is a “Programmable Logic Controller”. This is essentially a ruggedized mini-computer that sits out in the field within a panel, with a bunch of inputs and outputs leading from devices in the field into the PLC. The PLC will monitor the state of these inputs (e.g., the speed of a motor) and, depending on the programme inside, programmatically output various signals to control these field devices (e.g., stop the motor).
SCADA systems sit “on top” of programmable logic controllers. PLCs are almost always part of a SCADA network and form an interface between the field and SCADA. The data that is logged and stored in a SCADA system is typically acquired through communication with the PLC. The PLC will continue to execute its programme, reading inputs and writing outputs.
The SCADA system is used to keep a log of the historical state of these inputs and outputs, which can be used for data analysis or auditing. Programmable logic controllers have a limited capacity for long-term data storage.
Although SCADA systems can be programmed to control certain aspects of the field, this is usually an unwanted situation. Ideally, your PLC would run autonomously, able to programmatically handle any situation it encounters. Due to the complexity of the real world, this is often not the case. In these cases, operator input is required for the correct functioning of these semi-autonomous systems.
Hence, the level of “control” on the SCADA screen (i.e., HMI software) that the operator interacts with is generally much less than the control executed by a PLC. Anything that can be easily programmed into logic (e.g., IF the flow rate exceeds 100 metres per second, STOP the pump) will be programmed into the PLC.
So SCADA systems are primarily used for monitoring and data acquisition, with control capabilities used under irregular or complex circumstances. SCADA allows operators (and control systems engineers) to see an overview of the plant from a distance, giving them the ability to respond to any abnormal states. It should be noted that a SCADA system technically includes PLCs, which SCADA will communicate with.
A PLC sits in the field and will read field inputs (e.g., conveyor belt has stopped) and write outputs (e.g., start conveyor belt) depending on how it is programmed. A PLC forms part of a SCADA network, asynchronously receiving and executing certain commands from SCADA (e.g., operator commands to stop the pump), as well as being read by a SCADA network as a source of data.