Field Oriented Control

💡
Key learnings:
  • Field Oriented Control Defined: Field oriented control is a sophisticated technique that manages AC induction motors by independently controlling torque and magnetic flux, similar to DC motors.
  • Working Principle: The core of field oriented control lies in transforming three-phase motor inputs into two-dimensional vectors, simplifying the control over motor dynamics.
  • Control Transformations: Using Clarke and Park transformations, FOC converts AC inputs into a stable two-axis system, enabling precise manipulation of motor functions.
  • Advantages: Field oriented control offers significant benefits, including superior torque management, enhanced dynamic control at various speeds, and efficient energy consumption.
  • Application in Motors: FOC is adaptable for both synchronous and asynchronous motors, optimizing performance through detailed flux and speed adjustments.

AC Induction motors are known for their robustness, reliability, and ease of control, making them popular in everything from industrial systems to home appliances. Yet, achieving peak efficiency in these motors is tough due to their complex math models and non-linear behavior at saturation. This complexity necessitates high-performance control algorithms like vector control for effective management.

Introduction of Field Oriented Control

Scalar control, like the “V/Hz” strategy, falls short in performance, causing torque oscillations in induction motors. To enhance dynamic performance, a superior control method, such as Field Oriented Control (FOC), is essential. FOC, supported by modern micro-controllers and digital processors, effectively separates torque generation from magnetization, optimizing motor function.

Field Oriented Control directly manages motor torque and speed by focusing on its electromagnetic state, akin to a DC motor control strategy. FOC uniquely controls the crucial variables of torque and flux by separating stator current components, allowing independent control of the torque-producing component. This decoupling ensures that at low speeds, both motor magnetization and torque can be adjusted to maintain optimal performance.

“FOC has been solely developed for high-performance motor applications which can operate smoothly over the wide speed range, can produce full torque at zero speed, and is capable of quick acceleration and deceleration.”

Working Principle of Field Oriented Control

The field oriented control consists of controlling the stator currents represented by a vector. This control is based on projections that transform a three phase time and speed dependent system into a two coordinate (d and q frame) time invariant system. These transformations and projections lead to a structure similar to that of a DC machine control. FOC machines need two constants as input references: the torque component (aligned with the q coordinate) and the flux component (aligned with d coordinate).

The three-phase voltages, currents and fluxes of AC-motors can be analyzed in terms of complex space vectors. If we take ia, ib, ic as instantaneous currents in the stator phases, then the stator current vector is defined as follow:


Where, (a, b, c) are the axes of three phase system.

This current space vector represents the three phase sinusoidal system. It needs to be transformed into a two time invariant coordinate system. This transformation can be divided into two steps:
(a, b, c) → (α, β) (the Clarke transformation), which gives outputs of two coordinate time variant system.
(a, β) → (d, q) (the Park transformation), which gives outputs of two coordinate time invariant system.
The (a, b, c) → (α, β) Projection (Clarke transformation)
Three-phase quantities either voltages or currents, varying in time along the axes a, b, and c can be mathematically transformed into two-phase voltages or currents, varying in time along the axes α and β by the following transformation matrix:

Stator

Assuming that the axis a and the axis α are along same direction and β is orthogonal to them, we have the following vector diagram:

The above projection modifies the three phase system into the (α, β) two dimension orthogonal system as stated below:

But these two phase (α, β) currents still depends upon time and speed.
The (α, β) → (d.q) projection (Park transformation)
This is the most important transformation in the FOC. In fact, this projection modifies the two phase fixed orthogonal system (α, β) into d, q rotating reference system. The transformation matrix is given below:

Where, θ is the angle between the rotating and fixed coordinate system.
If you consider the d axis aligned with the rotor flux, Figure 2 shows the relationship from the two reference frames for the current vector:

Where, θ is the rotor flux position. The torque and flux components of the current vector are determined by the following equations:

These components depend on the current vector (α, β) components and on the rotor flux position. If you know the accurate rotor flux position then, by above equation, the d, q component can be easily calculated. At this instant, the torque can be controlled directly because flux component (isd) and torque component (isq) are independent now.

Basic Module for Field Oriented Control

Stator phase currents are measured. These measured currents are fed into the Clarke transformation block. The outputs of this projection are entitled isα and isβ. These two components of the current enter into the Park transformation block that provide the current in the d, q reference frame. The isd and isq components are contrasted to the references: isdref (the flux reference) and isqref (the torque reference). At this instant, the control structure has an advantage: it can be used to control either synchronous or induction machines by simply changing the flux reference and tracking rotor flux position. In case of PMSM the rotor flux is fixed determined by the magnets so there is no need to create one. Therefore, while controlling a PMSM, isdref should be equal to zero. As induction motors need a rotor flux creation in order to operate, the flux reference must not be equal to zero. This easily eliminates one of the major shortcomings of the “classic” control structures: the portability from asynchronous to synchronous drives. The outputs of the PI controllers are Vsdref and Vsqref. They are applied to the inverse Park transformation block. The outputs of this projection are Vsαref and Vsβref are fed to the space vector pulse width modulation (SVPWM) algorithm block. The outputs of this block provide signals that drive the inverter. Here both Park and inverse Park transformations need the rotor flux position. Hence rotor flux position is essence of FOC.
The evaluation of the rotor flux position is different if we consider the synchronous or induction motor.

  1. In case of synchronous motor(s), the rotor speed is equal to the rotor flux speed. Then rotor flux position is directly determined by position sensor or by integration of rotor speed.
  2. In case of asynchronous motor(s), the rotor speed is not equal to the rotor flux speed because of slip; therefore a particular method is used to evaluate rotor flux position (θ). This method utilizes current model, which needs two equations of the induction motor model in d,q rotating reference frame.
block diagram of indirect FOC

Simplified Indirect FOC Block Diagram

Classification of Field Oriented Control

FOC for the induction motor drive can be broadly classified into two types: Indirect FOC and Direct FOC schemes. In DFOC strategy rotor flux vector is either measured by means of a flux sensor mounted in the air-gap or by using the voltage equations starting from the electrical machine parameters. But in case of IFOC rotor flux vector is estimated using the field oriented control equations (current model) requiring a rotor speed measurement. Among both schemes, IFOC is more commonly used because in closed-loop mode it can easily operate throughout the speed range from zero speed to high-speed field-weakening.

Advantages of Field Oriented Control

  1. Improved torque response.
  2. Torque control at low frequencies and low speed.
  3. Dynamic speed accuracy.
  4. Reduction in size of motor, cost and power consumption.
  5. Four quadrant operation.
  6. Short-term overload capability.