ONLINE ELECTRICAL ENGINEERING STUDY SITE

Transformer Oil and Winding Temperature Rise Test

Temperature rise test of Transformer is included in type test of transformer. In this test we check whether the temperature rising limit of transformer winding and oil as per specification or not.

Temperature Rise Test for Top Oil of Transformer

  1. First the LV winding of the transformer is short circuited.
  2. Then one thermometer is placed in a pocket in transformer top cover. Other two thermometers are placed at the inlet and outlet of the cooler bank respectively.
  3. The voltage of such value is applied to the HV winding that power input is equal to no load losses plus load losses corrected to a reference temperature of 75oC.
  4. The total losses are measured by three wattmeters method.
  5. During the test, hourly readings of top oil temperature are taken from the thermometer already placed in the pocket of top cover.
  6. Hourly readings of the thermometers placed at inlet and outlet of the cooler bank are also noted to calculate the mean temperature of the oil.
  7. Ambient temperature is measured by means of thermometer placed around the transformer at three or four points situated at a distance of 1 to 2 meter from and half-way up the cooling surface of the transformer.
  8. Temperature rise test for top oil of transformer should be continued until the top oil temperature has reached an approximate steady value that means testing would be continued until the temperature increment of the top oil becomes less than 3oC in one hour. This steady value of top oil is determined as final temperature rise of transformer insulating oil.
  9. oil temperature rise test
  10. There is another method of determination of oil temperature. Here the test in allowed to be continued until the top oil temperature rise does not vary more than 1oC per hour for four consecutive hours. The least reading is taken as final temperature rise of the oil.
oil temperature rise During temperature rise test for top oil of transformer we make the LV winding short circuited and apply voltage to the HV winding. So for full load rated current flows in the transformer, the supply voltage required will much less than rated transformer voltage. We know that core loss of a transformer depends upon voltage. So there will not be any considerable core loss occurs in the transformer during test. But for getting actual temperature rise of the oil in a transformer, we have to compensate the lack of core losses by additional copper loss in the transformer. For supplying this total losses, transformer draws current from the source much more than its rated value for transformer.

Temperature rise limits of transformer when it is oil immersed, given in the table below

  Temperature rise limit
for air as
cooling medium
Temperature rise limit
for water as
cooling medium
Condition
Winding55oC60oCWhen oil circulation is natural

60oC65oCWhen oil circulation is forced

Top Oil50oC55oCWhen transformer is sealed &
equipped with conservator tank
45oC50oCWhen transformer is neither sealed
nor equipped with conservator tank
NB: These temperature rises limits mentioned in the above table are the temperature rise above the temperature of cooling medium. That means these are the difference between winding or oil temperature and temperature of cooling air or water.

Winding Temperature Rise Test on Transformer

  1. After completion of temperature rise test for top oil of transformer the current is reduced to its rated value for transformer and is maintained for one hour.
  2. After one hour the supply is switch off and short circuit and supply connection to the HV side and short circuit connection to the LV side are opened.
  3. But, the fans and pumps are kept running (if any).
  4. oil temperature rise
  5. Then resistance of the windings are measured quickly.
  6. But there is always a minimum 3 to 4 minutes time gap between first measurement of resistance and the instant of switching off the transformer, which can not be avoided.
  7. Then the resistances are measured at the same 3 to 4 minutes time intervals over a period of 15 minutes.
  8. Graph of hot resistance versus time is plotted, from which winding resistance (R2) at the instant of shut down can be extrapolated.
  9. From this value, θ2, the winding temperature at the instant of shut down can be determined by the formula given below-
    Where, R1 is the cold resistance of the winding at temperature t1.
For determining winding temperature rise we have to apply the above discussed indirect method. That means hot winding resistance is measured and determined first and then from that value we have to calculate the winding temperature rise, by applying resistance temperature relation formula. This is because unlike oil the winding of transformer is not accessible for external temperature measurement.



Closely Related Articles Transformer Testing | Type Test and Routine Test of TransformerTransformer Winding Resistance MeasurementVoltage and Turn Ratio Test of TransformerVector Group Test of Power TransformerOpen and Short Circuit Test on TransformerInsulation Dielectric Test of TransformerImpulse Test of TransformerMaintenance of TransformerSweep Frequency Response Analysis Test | SFRA TestInstallation of Power TransformerCommissioning of Power TransformerMore Related Articles What is transformer? Definition and Working Principle of TransformerEMF Equation of Transformer | Turns Voltage Transformation Ratio of TransformerIdeal TransformerTheory of Transformer on Load and No Load OperationResistance and Leakage Reactance or Impedance of TransformerEquivalent Circuit of Transformer referred to Primary and SecondaryHysteresis Eddy Current Iron or Core Losses and Copper Loss in TransformerVoltage Regulation of TransformerSingle Three Phase Transformer vs Bank of Three Single Phase TransformersParallel operation of TransformersMagnetizing Inrush Current in Power TransformerInstrument TransformersCurrent Transformer CT class Ratio Error Phase Angle Error in Current TransformerVoltage Transformer or Potential Transformer TheoryKnee Point Voltage of Current Transformer PS ClassAccuracy Limit Factor and Instrument Security Factor of Current TransformerIsolation TransformerTransformer Insulating Oil and Types of Transformer OilCauses of Insulating Oil DeteriorationCollecting Oil Sample from Oil Immersed Electrical EquipmentAcidity Test of Transformer Insulating OilDGA or Dissolved Gas Analysis of Transformer Oil | Furfural or Furfuraldehyde AnalysisPrinciple of Water Content Test of Insulating OilTransformer Accessories | Breather and Conservator Tank | RadiatorSilica Gel Breather of TransformerConservator Tank of TransformerRadiator of Transformer | Function of RadiatorMagnetic Oil Gauge or MOG | Magnetic Oil Level Indicator of TransformerOil Winding and Remote Temperature Indicator of TransformerTransformer Cooling System and MethodsOn Load and No Load Tap Changer of Transformer | OLTC and NLTCTertiary Winding of Transformer | Three Winding TransformerCore of Transformer and Design of Transformer CoreRestricted Earth Fault Protection of Transformer | REF ProtectionBuchholz Relay in Transformer | Buchholz Relay Operation and PrincipleWhat is Earthing Transformer or Grounding TransformerDifferential Protection of Transformer | Differential RelaysOver Fluxing in TransformerElectrical Power Transformer | Definition and Types of TransformerStep Up TransformerStep Down TransformerWhat is Auto Transformer ?High Voltage TransformerDistribution Transformer | All Day Efficiency of Distribution TransformerDry Type TransformerAir Core TransformerDesign of Inductor in Switched Mode Power Supply SystemsDesign of High Frequency Pulse TransformerSingle Phase TransformerToroidal TransformerNew Articles Series and Parallel Inductors Electric PowerMeasurement of Losses in Shunt ReactorThree Phase Shunt ReactorMeasurement of Insulation ResistanceAmpere's Circuital Law
electrical engineering app