Location of Shunt Capacitors

💡
Key learnings:
  • Shunt Capacitors Definition: Shunt capacitors are devices installed in electrical systems to improve power factor by compensating for reactive power.
  • Installation Locations: Shunt capacitors can be installed at system buses, distribution points, and individual loads to enhance voltage profiles and reduce energy bills.
  • Bulk Capacitor Banks: Installing bulk capacitor banks at high voltage bus systems is a practical approach to manage complexity and cost, providing overall system benefits.
  • Pole-Mounted Capacitors: Pole-mounted capacitor banks are used in distribution systems to compensate for reactive power, with varying voltage ratings and capacities.
  • Location of Capacitors for Power Factor Improvement: Choosing the right location for capacitors is crucial for power factor improvement, balancing cost, complexity, and system benefits.

Power factor correction uses a shunt capacitor at system buses, distribution points or individual loads. Cost and control needs decide the site.
A load that switches on and off is often paired with a capacitor bank on that feeder. That branch-bank scheme corrects the feeder but does not cut losses on the primary system.
location of shunt capacitors

In that scheme each bank switches with its own load feeder, so reactive power follows the load. The scheme costs more because each feeder needs its own bank size.
Putting a bank at every load can raise local voltage and cut local losses and the local energy bill, but the mix of sizes makes the plant hard to build and maintain. A bulk bank on a high-voltage bus system is the usual workaround. Control of each load is coarser, yet the cost and layout are simpler. A capacitor bank at the load and a bank on the primary system each has a role. The system demand decides which mix to use.

Banks also appear on high-voltage ∑ HV systems and feeders, and on individual distribution circuits.

Distribution System Capacitor Bank

On a distribution feeder the bank often sits on a pole and supplies the reactive power of that feeder. The units hang on one of the poles that carry the line and join the overhead conductors through an insulated power cable. Cable size follows the circuit voltage. Pole-mounted banks appear on low-voltage industrial circuits and on medium-voltage feeders, including many 440 V to 33 kV examples, with ratings from a few hundred kvar into the megavar range. Those figures are typical installations, not a standard limit. IEEE 18 lists shunt units from 216 V and 2.5 kvar upward. The bank may be fixed or switched as the load varies.

EHV Shunt Capacitor

On an extra-high-voltage system, generated electrical power may travel a long transmission line. Line inductance then produces a voltage drop that an ∑ HV capacitor bank at the ∑ HV substation can offset. The drop is largest at peak load, so that bank needs switching so it can be taken off when the line is light.

Substation Capacitor Bank

When a high-voltage or medium-voltage substation feeds a large inductive load, one or more banks at the substation can supply the inductive var of that load. Those banks are switched by a circuit breaker and are fitted with lightening arrestors. A typical protection scheme and relays sit with them.

Metal Encoder Capacitor Bank

Small industrial substations can also use indoor banks in a metal cabinet. The layout is compact and the bank needs less outdoor maintenance. Indoor use is common because the units are not left open to weather.

Distribution Capacitor Bank

Distribution banks are usually pole-mounted units near the load or at a distribution substation.
They do not raise the power factor of the primary system. They cost less than large transmission banks. A pole-mounted bank cannot carry every protection scheme used on a substation bank. The units are outdoor gear, though some sit in a metal enclosure against weather.

Fixed Capacitor Bank

Some loads, especially industrial ones, draw a steady reactive load for power factor correction. A fixed bank has no on/off control of its own. It stays connected for as long as its feeder is live.

Switched Capacitor Banks

On a high-voltage power system, most of the extra reactive demand appears at peak load. A bank left in at light load can push the system toward a leading power factor and raise voltage.
In that case the bank must switch on when load is high and power factor is poor, and switch off when load is light. A switched capacitor bank then supplies a fairly steady block of vars while it is in. That holds the desired power factor at peak load and avoids overvoltage at light load because the bank is off. While it is in, it also cuts losses on the feeders and on the transformer when the bank sits on the primary system.