- Current Transformer Definition: A current transformer (CT) is defined as an instrument transformer where the secondary current is proportional to the primary current and ideally has zero phase difference.
- CT Accuracy Class: The accuracy class of a current transformer measures how accurately the CT replicates the primary current in its secondary, crucial for precise metering.
- Working Principle: Current transformers operate on the principle of a power transformer, where the primary current is the system current, and the secondary current depends on the primary current.
- Ratio Error in Current Transformer: Ratio error in current transformer occurs when the primary current isn’t perfectly mirrored in the secondary current due to core excitation.
- Reducing CT Errors: Errors in current transformers can be reduced by using high-quality core materials, matching the rated burden with the actual burden, and minimizing the core length.
Definition of Instrument Transformer
Instrument transformers means current transformer and voltage transformer are used in electrical power system for stepping down currents and voltages of the system for metering and protection purpose. Actually relays and meters used for protection and metering, are not designed for high currents and voltages.
High currents or voltages in electrical power system cannot be directly fed to relays and meters. A current transformer steps down the system current to 1 Amp or 5 Amp, and a voltage transformer steps down system reduces the voltage to 110 V. Relays and meters are generally designed for 1 Amp, 5 Amp, and 110 V.
What is a Current Transformer?
A current transformer (CT) is an instrument transformer in which the secondary current is substantially proportional to primary current and differs in phase from it by ideally zero degree.
CT Accuracy Class or Current Transformer Class
A current transformer is similar to a electrical power transformer to some extent, but there are some difference in construction and operation principle. For metering and indication purpose, accuracy of ratio, between primary and secondary currents are essential within normal working range. Normally accuracy of current transformer required up to 125% of rated current; as because allowable system current must be below 125% of rated current.
Rather it is desirable the current transformer core to be saturated after this limit since the unnecessary electrical stresses due to system over current can be prevented from the metering instrument connected to the secondary of the current transformer as secondary current does not go above a desired limit even primary current of the current transformer rises to a very high value than its ratings. So accuracy within working range is main criteria of a current transformer used for metering purpose. The degree of accuracy of a metering current transformer is expressed by current transformer accuracy class or simply current transformer class or CT class.
But in the case of protection, the current transformer may not have the accuracy level as good as metering current transformer although it is desired not to be saturated during high fault current passes through primary.
So core of protection current transformer is so designed that it would not be saturated for long range of currents. If saturation of the core comes at lower level of primary current the proper reflection of primary current will not come to secondary, hence relays connected to the secondary may not function properly and protection system losses its reliability.
Imagine you have a current transformer with a ratio of 400/1 A, and its protection core saturates at 500 A. If the primary current reaches 1000 A, the secondary current will remain at 1.25 A due to saturation. If the relay connected to the secondary circuit requires 1.5 A to actuate, it will not operate, even if the primary current is 1000 A.
The degree of accuracy of a protection current transformer may not be as fine as metering current transformer but it is also expressed by current transformer accuracy class or simply current transformer class or CT class as in the case of metering current transformer but in little bit different manner.
Theory of Current Transformer or CT
A CT operates on the same basic principle as an electrical power transformer, but with some differences. In a power transformer, the primary current varies with the load or secondary current. In a CT, the primary current is the system current, which transforms to the CT secondary, making the secondary current dependent on the primary current.
In a power transformer, if the load is disconnected, only the magnetizing current flows in the primary. The primary current of a power transformer is proportional to the load connected to the secondary. However, in a CT, the primary is connected in series with the power line, so the primary current is the same as the current flowing through the power line.
The primary current of the CT, hence does not depend upon whether the load or burden is connected to the secondary or not or what is the impedance value of burden. Generally CT has very few turns in primary where as secondary turns is large in number. Say Np is number of turns in CT primary and Ip is the current through primary. Hence, the primary AT is equal to NpIp AT.
f number of turns in secondary and secondary current in that current transformer are Ns and Is respectively then Secondary AT is equal to NsIs AT.
In an ideal CT the primary AT is exactly is equal in magnitude to secondary AT.
So, from the above statement it is clear that if a CT has one turn in primary and 400 turns in secondary winding, if it has 400 A current in primary then it will have 1 A in secondary burden.
Thus the turn ratio of the CT is 400/1 A
Current Transformer Error
But in an actual Current Transformer (CT), errors with which we are connected can best be considered through a study of phasor diagram for a CT,
Is – Secondary current.
Es – Secondary induced emf.
Ip – Primary current.
Ep – Primary induced emf.
KT – Turns ratio = Numbers of secondary turns/number of primary turns.
I0 – Excitation current.
Im – Magnetizing component of I0.
Iw – Core loss component of I0.
Φm – Main flux.
Let us take flux as reference. EMF Es and Ep lags behind the flux by 90°. The magnitude of the passers Es and Ep are proportional to secondary and primary turns. The excitation current Io which is made up of two components Im and Iw.
The secondary current I0 lags behind the secondary induced emf Es by an angle Φ s. The secondary current is now transferred to the primary side by reversing Is and multiplied by the turns ratio KT. The total current flows through the primary Ip is then vector sum of KT Is and I0.
The Current Error or Ratio Error in Current Transformer or CT
From above passer diagram it is clear that primary current Ip is not exactly equal to the secondary current multiplied by turns ratio, i.e. KTIs. This difference is due to the primary current is contributed by the core excitation current. The error in current transformer introduced due to this difference is called current error of CT or some times ratio error in current transformer.
Phase Error or Phase Angle Error in Current Transformer

For an ideal CT, the angle between the primary and reversed secondary current vector is zero. However, in a real CT, there is always a phase difference because the primary current also supplies the excitation current. This phase difference is called the phase angle error in a current transformer.
Here in the pharos diagram it is β the phase angle error is usually expressed in minutes.
Cause of Error in Current Transformer
The total primary current is not actually transformed in CT. One part of the primary current is consumed for core excitation and remaining is actually transformers with turns ratio of CT so there is error in current transformer means there are both ratio error in current transformer as well as a phase angle error in current transformer.
How to Reduce Error in Current Transformer
It is desirable to reduce these errors, for better performance. For achieving minimum error in current transformer, one can follow the following,
- Using a core of high permeability and low hysteresis loss magnetic materials.
- Keeping the rated burden to the nearer value of the actual burden.
- Ensuring minimum length of flux path and increasing cross-sectional area of the core, minimizing joint of the core.
- Lowering the secondary internal impedance.