electrical4u.com logo Home MCQ Engineering Calculators Videos Basic Electrical Circuit Theories Electrical Laws Materials Batteries Illumination Generation Transmission Distribution Switchgear Protection Measurement Control System Utilities Safety Transformer Motor Generator Electrical Drives Electronics Devices Power Electronics Digital Electronics Biomedical Instrumentation

Restricted Earth Fault Protection of Transformer | REF Protection

Published on 24/2/2012 and last updated on Friday 13th of July 2018 at 07:40:54 AM

Restricted Earth Fault Protection of Transformer

An external fault in the star side will result in current flowing in the line current transformer of the affected phase and at the same time a balancing current flows in the neutral current transformer, hence the resultant current in the relay is therefore zero. So this REF relay will not be actuated for external earth fault. But during an internal fault, the neutral current transformer only carries the unbalance fault current and operation of Restricted Earth Fault Relay takes place. This scheme of restricted earth fault protection is very sensitive for internal earth fault of electrical power transformer. The protection scheme is comparatively cheaper than differential protection scheme.
Restricted earth fault protection is provided in electrical power transformer for sensing internal earth fault of the transformer. In this scheme, the CT secondary of each phase of an electrical power transformer are connected together as shown in the figure. Then common terminals are connected to the secondary of a Neutral Current Transformer or NCT.

The CT or Current Transformer connected to the neutral of a power transformer is called Neutral Current Transformer or Neutral CT or simply NCT. Whenever there is an unbalancing in between three phases of the power transformer, a resultant unbalance current flow through the closed path connected to the common terminals of the CT secondaries. An unbalance current will also flow through the neutral of the power transformer and hence there will be a secondary current in Neutral CT because of this unbalance neutral current. In Restricted Earth Fault scheme the common terminals of phase CTs are connected to the secondary of Neutral CT in such a manner that secondary unbalance current of phase CTs, and the secondary current of Neutral CT will oppose each other. If these both currents are equal in amplitude there will not be any resultant current circulates through the said closed path. The Restricted Earth Fault Relay is connected in this closed path. Hence the relay will not respond even there is an unbalancing in-phase current of the power transformer.

restricted earth fault protection

REF protection of transformers restricted earth fault protection of power transformer

Related pages
Restricted Earth Fault Protection of Transformer | REF Protection
Please Rate this Article
4.5
⚑ 4 total
5
4
3
2
1


New Articles
Articles on Transformer Protection
Buchholz Relay Differential ProtectionREF ProtectionOver Fluxing
More Articles on Transformer
Electric MachinesTransformer BasicsSingle Phase TransformerThree Phase TransformerTransformer TypeInstrument TransformerTransformer TestInstallation of TransformerTransformer AccessoriesTransformer OilMaintenance of Transformer
Articles Categories
Home
Basic Electrical
Electric Transformer
Electric Generator
Electric Motor
Electrical MCQ
Engineering Calculators
Video Lectures
Electrical Generation
Electric Transmission
Switchgear
Electric Protection
Electrical Measurement
Electronics Devices
Power Electronics
Digital Electronics