- Steam Consumption Definition: Steam consumption is the difference between the steam generated and the steam utilized at the point of use.
- Importance of Calculation: Knowing how to calculate steam consumption helps save costs on water, coal, and electricity.
- Warm-Up Load: This refers to the steam required to heat the system from a cold start to its normal operating temperature.
- Condensation Factors: The rate of steam condensation is influenced by the mass, specific heat, temperature increase, and warm-up time.
- Calculation Method: The formula for calculating steam consumption during warm-up involves parameters like steam temperature, ambient temperature, and specific heat of the pipe material.
What is Steam Consumption in a Pipe?
Steam consumed and steam utilized at the application point are not the same. Typically, steam generated in a steam boiler exceeds the amount needed at the point of use.
The difference in steam consumption and steam utilization is due to:
- Steam condensation when it travels on its way to point of use mainly due to exposed surfaces.
- Leakages (if any)
When steam condenses on the wall of an exposed/uninsulated steam pipe, it gives up its enthalpy of evaporation.
Proper utilization of steam helps in saving in the input cost of water and coal. Saving of each kg of steam is directly proportional to the saving of some percentage of water, coal and electricity.
We can calculate steam consumption during both start-up and normal operation. The details are discussed below.
Steam Consumption in Steam Mains
Steam consumption within the pipe system needs to be judiciously monitored and controlled. The rate of condensation of the steam in the steam piping network depends upon the type of load (i.e. warm-up load or running load).
The rate of condensation of steam needs to be taken into account for sizing the steam traps, and also in finalizing the boiler output.
What is Warm-Up Load ?
During the plant start-up after a long time or from cold, then the steam is required to heat the system uniformly to bring the system close to the normal working temperature of the system.
The ‘warm-up load’ is the steam load which is associated with the steam consumption during the start-up of the plant. This can be either from the cold shut down, or from start-up after a very long time.
The rate of steam condensation is highest during the warm-up period. Steam traps should be designed based on this load.
A good practice is to warm-up the system very slowly for safety-reasons, pipes have the benefit of reduced thermal and mechanical stress. Thus results in the following benefits:
- Eliminations of leaks
- Lower-maintenance-costs
- Longer life for the pipes
- No water hammer.
What is Process Plant Running Load?
Process plant running load is the steam load which is related to the normal (full load) continuous load of the plant. The rate of condensation of steam during the full load running a load of the plant is minimum.

How to Warm-Up a System?
Uniform and slow system warm-up can be achieved by a small by-pass valve in parallel to the main line isolation valve.
The time required to warm up the pipe network decides the warm-up (bypass) valve size. This valve can be a manual or automatic type depending on the user/client.
Avoid using the main valve for warm-up as it is designed for full flow and not suitable for small flow during warm-up. Use the bypass valve instead.
As shown in figure1 above, before the main valve/bypass valve separator is installed to ensure that steam passing through the valve should be dry to protect the valve wear and tear.
If we provide sufficient time for the warming-up, then it is possible to get the following benefits:
- For minimizing the pipe stress
- For operational safety
- Reduce start-up loads on boiler
The steam flowrate required to bring a pipework system up to operating temperature is a function of:
- Mass
- Specific heat of the material
- Temperature increase
- Enthalpy of evaporation of steam or Enthalpy of saturated steam
- Allowable time

Where:
- ms: Mean rate of condensation of steam in kg/hr
- W: Total weight of pipe plus flanges and fittings in kg
- Ts: Steam temperature oC
- Tamb: Ambient temperature
- Cp: Specific heat of pipe material in kj/kgoC
- hfg: Enthalpy of evaporation or saturated enthalpy at operating pressure in kj/kg
- t: Time of warming-up in minutes
Note: Suppose if the warm-up/heating time of the system is increased to 12 minutes from 6 minutes, then the initial flow rate of the steam can easily be reduced to half. If the warm-up/heating time of the system is increased to say 24 minutes, then the initial steam flow rate for heating can be reduced further.
Method to calculate the warm-up condensing load for a period of 30 minutes in a steam system
Let:
- The system consists of carbon steel pipe of size — 150 mm
- Steam Pressure — 16 bar(g)
- Steam temperature (Ts) — 201oC
- Enthalpy of evaporation corresponding to above parameters hfg — 1933
- Ambient air temperature (Tamb) — 20oC
- Length of the pipe shall be — 120 m
- Cp of steel is —- 0.49 kj/kgo C
- Warming-up time in minutes (t) — 30
- Total weight of pipe plus flanges and fittings in kg (W)
- Pipe network consists of 10 pairs of PN-40 flanged joints and two isolation valves
Table 1: Typical weights of steel pipe, flanges and bolts, and isolating valves in kg.
| Pipe size(mm) | Sch.40 pipe kg/m | Flange weight per pair | Isolating valve flanged PN40 | ||
| PN40 | ANSI150 | ANSI300 | |||
| 150 | 28.2 | 28.0 | 26.0 | 32 | 88 |
To find W, find the mass of the various steam main items from Table 1
- 150 mm steel main = 28.2 kg/m
- 150 mm flanges to PN-40 = 28 kg per pair
- 150 mm stop valve = 88 kg each

Rate of condensation generated during warm-up time is given by: