- Equivalent Circuit Definition: An equivalent circuit of a transformer is a simplified model used to calculate impedance, resistance, and leakage reactance.
- Primary Side Equivalent Circuit: To draw the equivalent circuit referred to the primary side, use the general equivalent circuit and modify it for primary side calculations.
- Excitation Branch: The primary current splits into no-load and load components, requiring a parallel path in the equivalent circuit known as the excitation branch.
- Approximate Equivalent Circuit: The excitation circuit can be ignored for simplification, combining resistance and reactance into equivalent values referred to the primary side.
- Secondary Side Equivalent Circuit: The equivalent circuit can also be referred to the secondary side, following similar steps as for the primary side.
What is the Equivalent Circuit of a Transformer?
The equivalent circuit diagram of a transformer simplifies the calculation of impedance, resistance, and leakage reactance.
Calculating the equivalent impedance of transformer is essential. This calculation uses the equivalent circuit referred to the primary or secondary side. The percentage impedance is also a key parameter.
Pay special attention to percentage impedance when installing transformers in an electrical system. Matching the percentage impedance is crucial for parallel operation of power transformers.
The percentage impedance can be derived from the equivalent impedance of the transformer so, it can be said that the equivalent circuit of the transformer is also required during the calculation of the % impedance.
Equivalent Circuit of Transformer Referred to Primary

For drawing equivalent circuit of transformer referred to primary, first we have to establish general equivalent circuit of transformer then, we will modify it for referring from primary side. For doing this, first we need to recall the complete vector diagram of a transformer which is shown in the figure below.
Let us consider the transformation ratio be,
In the figure above, the applied voltage to the primary is V1 and voltage across the primary winding is E1. Total current supplied to primary is I1. So the voltage V1 applied to the primary is partly dropped by I1Z1 or I1R1 + j.I1X1 before it appears across primary winding.

The voltage appeared across winding is countered by primary induced emf E1. So voltage equation of this portion of the transformer can be written as,
The equivalent circuit for that equation can be drawn as below,
From the vector diagram above, it is found that the total primary current I1 has two components, one is no – load component Io and the other is load component I2′. As this primary current has two components or branches, so there must be a parallel path with primary winding of transformer.
This parallel path of current is known as excitation branch of equivalent circuit of transformer. The resistive and reactive branches of the excitation circuit can be represented as


The load component I2′ flows through the primary winding of transformer and induced voltage across the winding is E1 as shown in the figure right.
This induced voltage E1 transforms to secondary and it is E2 and load component of primary current I2′ is transformed to secondary as secondary current I2. Current of secondary is I2.

So the voltage E2 across secondary winding is partly dropped by I2Z2 or I2R2 + j.I2X2 before it appears across load. The load voltage is V2.
The complete equivalent circuit of transformer is shown below.

Now if we see the voltage drop in secondary from primary side, then it would be ′K′ times greater and would be written as K.Z2.I2.
Again I2′.N1 = I2.N2
Therefore,
From above equation, secondary impedance of transformer referred to primary is,
So, the complete equivalent circuit of transformer referred to primary is shown in the figure below:
If you’d like to study more electrical questions like this, check out our MCQs on transformers.
Approximate Equivalent Circuit of Transformer
Since Io is very small compared to I1, it is less than 5% of full load primary current, Io changes the voltage drop insignificantly.
Hence, it is good approximation to ignore the excitation circuit in approximate equivalent circuit of transformer.

The winding resistance and reactance being in series can now be combined into equivalent resistance and reactance of transformer, referred to any particular side. In this case it is side 1 or primary side.
Equivalent Circuit of Transformer Referred to Secondary
In a similar way, the approximate equivalent circuit of transformer referred to secondary can be drawn.

Where equivalent impedance of transformer referred to secondary, can be derived as

