- Distribution Transformer Definition: A distribution transformer is defined as a step-down transformer used to distribute electric power efficiently to consumers.
- Types of Distribution Transformers: These include single phase, three phase, pole mounted, pad mounted, and underground transformers, each serving different purposes.
- Secondary Terminals: Deliver electrical power to consumers and are connected through a fuse unit for protection against faults.
- All Day Efficiency of Transformer: This efficiency is the ratio of total energy delivered to the energy fed over 24 hours, considering the varying loads throughout the day.
- Losses in Transformers: Transformers experience iron losses (constant) and copper losses (varying with load), impacting overall efficiency.
Distribution Transformer
The step down transformers used for electric power distribution purpose are referred as distribution transformer. There are several types of transformer used in the distribution system. Such as single phase transformer, three phase transformer, pole mounted transformer, pad mounted transformer, and underground transformer. Distribution transformers are generally small in size and filled with insulating oil. These transformers are available in the market in various sizes and efficiencies. Selection of distribution transformer depends upon the purpose and budget of the end users.
Secondary Terminals of Distribution Transformer
Secondary terminals of distribution transformer deliver electrical power at a utilization voltage level to the consumer end via energy metering system. In case of three phase distribution system three phase four wire secondary systems are adopted. Here, three phases, which means red, yellow and blue phase conductors, come out from three low voltage bushing studs of the transformer. The neutral wire is connected to the fourth bushing which is also referred as a neutral bushing of the transformer.
The neutral point of a distribution transformer originates from the tie point of the three-phase winding inside the transformer. For industrial heavy loads, a four-wire system is directly delivered to the consumer. For single phase light loads, one phase and a neutral connection from the three-phase distribution transformer connect to the consumer’s energy meter.
The secondary terminals of a distribution transformer first connect to a three-phase bus in a nearby distribution kiosk. This connection is made through a fuse unit for fault protection. From this bus, different three-phase or single-phase service mains or sub-distributors are connected.
A typical type of-single phase system is available in United State of America for supplying single phase residential tons. Here, single phase pole mounted transformer is used for supplying single phase residential load. This type pole mounted transformer has total three secondary terminals, one of which is ground and other two are phase terminals. Two phase wires provide 240 volts across them, and the voltage across any of the phase wire and the ground wire is 120 volts. So a consumer can be supplied either of 240 volts or 120 volts supply depending upon his requirement. Actually in this system, the secondary winding of the distribution transformer is center tapped. The center wire is grounded and marked as neutral. The two end conductors of the winding is called hot wire.
Efficiency of Distribution Transformer
The efficiency of a distribution transformer is defined as the ratio of output power to input power at full load. However, distribution transformers rarely run at full load. Their efficiency is highest at around 50% load.
A transformer has mainly two types of losses, these are, iron losses and copper losses. Iron loss, which is also referred as core loss, consists of hysteresis loss and eddy current loss. These two losses are constant when the transformer is charged. That means the amount of these losses does not depend upon the condition of secondary load of the transformer. In all loading condition, these are fixed. But the copper loss which is also referred as I2R loss entirely depends upon load I. A distribution transformer cannot be run with constant load throughout 24 hours. At day peak time it’s loading is high, whereas in night lean time its loading may be negligible.
So selecting a transformer depending upon its conventional efficiency is not practical and economical, too. As a solution of these problems, the concept of all day efficiency of distribution transformer came into the picture. So this efficiency is same as the efficiency of distribution transformer.
In this concept, we use the ratio of total energy delivered by the transformer to the total energy fed to the transformer, during a 24 hrs span of time instead of ratio of power output and input of the transformer. Hence, all day efficiency is determined as, total KWh at the secondary to the total KWh at the primary of the transformer for a long specific time period preferably 24 hrs. i.e,

This is very much useful to judge the performance of a distribution transformer, whose primary is connected to the system forever, but secondary load varies tremendously throughout the day.


Could you please forward me a pdf for these posted informations.Thank you for posting such a wonderful materials for we the electrical engineering students
I really appreciate your efforts.
I want more pdf.
Am Philip Agyemang,an Electrical and Electronics Engineering student
Very happy to hear our work has helped you Philip. We are currently looking at integrating downloadable pdf versions for all of our articles.
In the meantime, I have emailed you the pdf of this article – I hope that helps!