Single Phase Power | Active Reactive and Apparent Power

Single Phase Power

A single phase transmission system is practically not available, but still we should know the basic concept of single phase power first before going through modern three phase power system.

Before going to details about single phase power, let's try to understand different parameters of electrical power system.

Three basic parameters of electrical power system are electrical resistance, inductance and capacitance.

Resistance

The resistance of power circuit or simple resistor consumes ohmic energy. While electric current flows through a resistor, there will not be any phase difference between the voltage and current, which means electric current and voltage are in same phase; the phase angle between them is zero. If I current flows through an electrical resistance R for t seconds, then total energy consumed by the resistor is I2.R.t. This power is known as active power.

Inductance

Inductance of the system or simple inductor stores magnetic field energy during positive half cycle and gives away during negative half cycle of single phase power supply. If a current 'I' flows through a coil of inductance L Henri, the energy stored in the coil in form of magnetic field is given by

The power associated with an inductance is reactive power.

Capacitance

Capacitance of the system or simply capacitor, stores static electric field energy during positive half cycle and give away during negative half cycle of supply. The energy stored between two parallel metallic plates of electric potential difference V and capacitance across them C, is expressed as

This energy is stored in form of static electric field. The power associated with a capacitance is also reactive power.

Active Power and Reactive Power

Let us consider a single phase power circuit in which current lags behind the voltage by an angle φ.
Let the instantaneous voltage v = Vm.sinωt

Then the instantaneous current can be expressed as i = Im. sin(ωt - φ).

Where, Vm and Im are the maximum values of sinusoidal system voltage and current respectively.

The instantaneous power is given by

Active Power

Resistive Power

Let's take the condition first where the single phase power circuit is fully resistive, that means the phase angle between voltage and current i.e. φ = 0 and hence,


active power

From the above equation it is clear that, whatever may be the value of ωt the value of cos2ωt cannot be greater than 1; hence the value of p cannot be negative. The value of p is always positive irrespective of the instantaneous direction of voltage v and current i, that means the energy is flowing in its conventional direction, i.e. from source to load and p is the rate of energy consumption by the load and this is called active power. As this power is consumed due to resistive effect of an electrical circuit, hence sometimes it is also called resistive power.

Reactive Power

Inductive Power

Now consider a situation when the single phase power circuit is fully inductive, that means the current lags behind the voltage by an angle φ = + 90o. Putting φ = + 90o

inductive power
In the above expression, it is found that the power is flowing in alternative directions. From 0° to 90° it will have negative half cycle, from 90° to 180° it will have positive half cycle, from 180° to 270° it will have again negative half cycle and from 270° to 360° it will have again positive half cycle. Therefore this power is alternative in nature with a frequency, double of supply frequency. As the power is flowing in alternating direction i.e. from source to load in one half cycle and from load to source in next half cycle, the average value of this power is zero. Therefore this power does not do any useful work. This power is known as reactive power. As the above explained reactive power expression is related to fully inductive circuit, this power is also called inductive power.

This can be concluded as if the circuit is purely inductive, energy will be stored as magnetic field energy during positive half cycle and give away during negative half cycle and rate at which this energy changes, expressed as reactive power of inductor or simply inductive power and this power will have equal positive and negative cycle and the net value will be zero.

Capacitive Power

Let us now consider the single phase power circuit is fully capacitive, that is the current leads the voltage by 90°, therefore φ = - 90°.


capacitive power

Hence in the expression of capacitive power, it is also found that the power is flowing in alternative directions. From 0° to 90° it will have positive half cycle, from 90° to 180° it will have negative half cycle, from 180° to 270° it will have again positive half cycle and from 270° to 360° it will have again negative half cycle. So this power is also alternative in nature with a frequency, double of supply frequency. Therefore, as inductive power, the capacitive power does not do any useful work. This power is also a reactive power.

Active Power & Reactive Power

The power equation can be re-written as

This above expression has two consonants; first one is Vm. Im.cosφ(1 – cos2ωt) which never goes negative as because value of (1 – cos2ωt) always greater or equal zero but cannot have a negative value.
active power and reactive power
This portion of the single phase power equation represents the expression of reactive power which is alternatively known as real power or true power. The average of this power will obviously have some non zero value means, the power physically does some useful work and that is why this power is also called real power or sometimes it is referred as true power. This portion of the power equation represents the reactive power which is alternatively known as real power or true power.

Second term is Vm. Im.sinφsin2ωt which will have negative and positive cycles. Hence, average of this component is zero. This component is known as reactive component as it travels back and forth on the line without doing any useful work.

Both active power and reactive power have same dimensions of watts but to emphasize the fact that reactive component represents a non-active power, it is measured in terms of volt-amperes reactive or in short VAR.