ONLINE ELECTRICAL ENGINEERING STUDY SITE

How to Test Capacitors?

Capacitors, we all know that they are charge storing devices. It should have to be checked and tested during servicing or troubleshooting in almost all the Electrical and Electronics circuits. For testing the capacitors, different methods are adapted. They are briefed below.

Traditional Method to Test Capacitors

This method is really dangerous and is recommended only for professional Electrical engineer. For this method, it is safe to use 24V DC or 220-224V AC than 230V AC.

If 220-224V AC is used, series resistors should be connected in between the capacitor. traditional method to test capacitors The procedure is as follows:

  1. The capacitor to be tested should be disconnected or minimum one lead of the suspected capacitor should be disconnected.
  2. The capacitor should completely in discharge condition.
  3. The leads should be connected to the terminal of capacitor.
  4. Next, these leads should be connected for a very short time (1- 4 seconds) to 230V AC supply.
  5. Now, remove the leads from the supply.
  6. This is the important and most dangerous step. Short the terminals of the capacitor.
  7. We can see that when the capacitor is good, a strong spark is produced.
  8. When the capacitor is bad or not in good condition, a weak spark is produced.

By Using Ohmmeter Setting Mode of a Multimeter

This method is used for finding the resistance of the capacitor and finding the condition of capacitor (Figure 2). using Ohmmeter setting mode of a Multimeter The procedure is as follows:
  1. The capacitor to be checked must have to be in discharged condition.
  2. The multimeter should be in ohmmeter setting.
  3. Now, connect the leads of the meter to the terminals of the capacitor.
  4. The reading should be noted and the result should be compared with the following.
  5. The low resistance value indicates short capacitor.
  6. If there is no deflection in meter; that means, it is an open capacitor.
  7. When there is a condition that at first the meter shows a low resistance and then it increases progressively to infinite, then it is a good capacitor.

By Using Capacitance Setting Mode of a Multimeter

This is the simplest and excellent method for checking the capacitor (Figure 3). using capacitance setting mode of a Multimeter The procedure is as follows:
  1. The capacitor to be checked must have to be in discharged condition.
  2. The multimeter should be in capacitance setting.
  3. Now, connect the leads of the meter to the terminals of the capacitor. The polarity is not a concern here.
  4. The capacitance value which is almost near the capacitance rating of the suspected capacitor is shown in the meter.
  5. If the capacitor is defective, we can see a lower value of capacitance or no values in the meter.

By using Voltmeter to Test Capacitors

This method is used to find the potential difference between across the capacitor. The procedure is as follows:
  1. The capacitor is first charged with DC voltage which is less than the capacitor rating.
  2. The polarity is important here. The longer lead (anode) of the capacitor to be connected to positive voltage and shorter lead (cathode) is connected to ground or negative terminal of voltage.
  3. The terminals of the voltmeter should be connected across the terminals of the capacitor.
  4. When it reads the same voltage as we charged and afterwards declines, then the capacitor is in good condition.
  5. When the capacitor is not getting charged and the voltmeter shows reading, then the capacitor is not good or in defective condition.
The above four tests are implemented for finding the capacitor effectiveness. That is to determine the condition of a capacitor.

Closely Related Articles
More Related Articles
New Articles